Solis S6-EH1P5K-L-PLUS Hybrid and Single-Phase Inverter
- 10 seconds of 200% overload capability
- Multiple inverters can operate together to form a microgrid
MODEL | S6-EH1P5K-L-PLUS |
---|---|
MAX. DC POWER | 10kW |
MAX. DC VOLTAGE(VDC) | 500 V |
START VOLTAGE | 90 V |
NOMINAL VOLTAGE | 330 V |
MPP VOLTAGE RANGE | 90 – 435 V |
NO. OF MPP TRACKERS | 2 / 2 |
MAX INPUT CURRENT | 16 A / 16 A |
MAX. SHORT-CIRCUIT CURRENT | 20 A / 20 A |
Battery type | Li-ion / Lead-acid |
Battery voltage range | 40 – 60 V |
Max. charge / discharge power | 5 kW |
Max. charge / discharge current | 112 A |
Communication | CAN / RS485 |
RATED OUTPUT POWER | 5 kW |
MAX. OUTPUT POWER | 5 kVA |
RATED GRID VOLTAGE | L/N/PE 220 V / 230 V |
RATED GRID FREQUENCY | 50 Hz / 60 Hz. |
RATED GRID OUTPUT CURRENT | 22.8 A / 21.8 A. |
MAX. OUTPUT CURRENT | 22.8 A / 21.8 A. |
POWER FACTOR | > 0.99 (0.8 leading – 0.8 lagging) |
THDI | <2% |
Input voltage range | 187 – 253 V |
Max. input current | 32 A |
Frequency range | 45 – 55 Hz / 55 – 65 Hz |
Rated output power | 5 kW |
Max. apparent output power | 2 times of rated power, 10 s. |
Back-up switch time | < 4 ms |
Rated output voltage | L/N/PE, 220 V / 230 V. |
Rated frequency | 50 Hz / 60 Hz. |
Rated output current | 22.8 A / 21.8 A. |
Max. AC passthrough current | 40 A. |
THDv (@linear load) | < 2% |
MAX.EFFICIENCY | 96.2% |
EUROPEAN EFFICIENCY | 96.1% |
BAT charged by PV / AC max. efficiency |
95.3% / 93.9% |
BAT discharged to AC max. efficiency | 93.8% |
DC REVERSE POLARITY PROTECTION | yes |
Ground fault monitoring | yes |
Integrated AFCI 2.0 | Optional |
Protection class / Over voltage category | I / II (PV and BAT) III (MAINS and BACKUP and GEN). |
DIMENSIONS (W × H × D) | 335 × 560 × 253 mm |
WEIGHT | 23 kg |
TOPOLOGY | High frequency isolation (for battery) |
SELF-CONSUMPTION (NIGHT) | < 1 W |
OPERATING AMBIENT TEMPERATURE RANGE | -40 ~ +60°C |
INGRESS PROTECTION | IP66 |
NOISE EMISSION (TYPICAL) | < 60 dB(A) |
COOLING CONCEPT | Natural cooling |
MAX. OPERATION ALTITUDE | 3000 m |
Safety / EMC standard | IEC/EN 62109-1/-2, EN 61000-6-2/-3. |
DC CONNECTION | MC4 plug (PV port) / Terminal Block (BAT port) |
AC CONNECTION | Terminal Block |
DISPLAY | 7.0″ LCD display & Bluetooth + APP. |
COMMUNICATION | RS485, CAN, Optional: Wi-Fi, GPRS, LAN. |
Grid connection standard
NRS 097-2-1/ IEC 62116 / IEC 61727 / IEC 60068, IEC 61683. EN 50530 / MEA / PEA / NBR16149 / NBR 16150.